Voltage Protection Relays & EOCRs

Products > Low Voltage Switchgear > Control Relays, Voltage Protection Relays & EOCRs > Schneider > Voltage Protection Relays & EOCRs

Voltage Protection Relays & EOCRs

SAMWHA EOCRs are used for over-current monitoring and tripping. The Relays are suitable for direct use from 0.5HP to 5HP (with a 6.5A relay) and up to 40HP (with a 60A relay), through CTs for motors of up to 500HP.

Type: EOCRSS05/60NU
Supply Voltage100VAC – 240VAC/DC
Contacts1C
Starting Delay Time Setting Range1 to 30 sec
Operating Time Setting Range0.5, 1 to 10sec
Contact Rating3A/250VAC
Load Current Setting Rangei.0.5A to6.5A, ii. 5A to 60A
Type: EOCRSS-05/60S
Supply Voltage24 – 240VAC/DC
Contacts1A+1B
Starting Delay Time Setting Range1 to 30 sec
Operating Time Setting Range0.5, 1 to
10 sec Contact Rating3A/250VAC
Load Current Setting Rangei.0.5A to 6.5A, ii.5A to60A

FEATURES

  • Over current Monitoring & Tripping: Suitable for direct use from 0.5HP to 5HP (with 6.5A relay) and up to 40 HP (with 60A relay) or through CTs up to 500HP motors (with 6.5A relay)
  • Protection against phase-loss (Single Phase operation)
  • Shock Relay
  • Ammeter Reading
  • No-Volt Relay
  • UL Approved
  • Mounting: Surface or DINRail
Type: EOCR-SSD
Supply Voltage220VAC ±15%
Starting Delay Time1 ~30sec
Trip Time0.5, 1~10sec
Contact Ratings2 –SPST, 3A250VAC
Load Current
  1. 5 ~6A
  2. 10 ~60A

Higher currents with external CT

FEATURES

  • Over current Monitoring & Tripping
  • MCU based, 2 CT type
  • Real Time processing & high precision
  • Digital Display: Trip cause/easy troubleshooting
  • Reset: Manual/Electrical
  • Load Selection 1 Phase or 3 Phase
  • Fail Safe: No Volt Relay selectable

FEATURES

  • MCU based, Real-time processing / HighPrecision
  • Three Integral Current Transformers “HoleTypes”
  • 3 TCC (Time –Current Characteristics)- Definite, Inverse and Thermal Inverse: Selectable
  • Thermal protection / Inverse TCC available up to 32A without external
  • Communication: Modbus /RS-485
  • Alert operation function: Aux, Flicker, Hold
  • Digital AmmeterReading
  • Reset: Manual / Auto / Electrical:Selectable
  • Trip Cause Memory: Stores up to 3 latest TripCauses
  • Available application on single and 3 PhaseMotor
  • No Volt Release Selectable
  • 5 digit 7-Segment LEDs display
  • Total Operation HoursRecording
  • Stall, Jam, Current imbalance Protection functions built-in
Type:EOCR-i3DM(Display Built-in), Mounting: Panel / Din-Rail With Over current, Undercurrent, Ammeter & Communication (RS485 Modbus) with Pre-Trip Alarm.

Specification

Supply Voltage100 ~240VAC/DC
Load Current Setting Range0.5 ~80A
Delay Time(D-Time)0 ~ 200sec
Operating Time(O-Time)0.2 ~ 30sec
Inverse & Thermal1 ~ 30classes
UndercurrentOFF,0.5~5s
Auto Reset0.5s~20min
Contact RatingsOverload: 1a1b, Pre trip (Al): 1a,(3A/250VAC)
Phase LossOFF, 0.5 ~ 5SAdjustable
Phase ReverseWithin 0.15s

For higher motor setting currents please use separate CT up to 800 / 5A

Type: EOCR-i3MS

  • With built-in display
  • Mounting: Panel / Din-Rail

Type:EOCR-iFMS

    • Display Separated
    • Mounting: Panel / Din-Rail / Flush Mount
    • With Overcurrent, Undercurrent, Short circuit Protection, Ammeter, and Communication (RS-485 Modbus)
Supply Voltage100 ~240VAC/DC
Load Current Setting Range0.5 ~ 25A (EOCR -I3MS)
0.5 ~ 60A (EOCR -IFMS)
Delay Time(D-Time)0 ~ 200sec
Operating Time(O-Time)0.2 ~ 30sec
Inverse & Thermal1 ~ 30classes
UndercurrentOFF,0.5~5s
Short Circuit Current SettingSc Setting 200 ~ 2200% of 0.5~10A current settingrange.
Adjustable Time Delay 0 ~ 30S, O-time: 0.05S Setting Range: 2~11 times for 20A.
Auto Reset0.5s~20min
Contact RatingsOverload: 1a1b, Short Circuit: 1a,(3A/250VAC)
Phase LossOFF, 0.5 ~ 5SAdjustable
Phase ReverseWithin 0.15s

For higher motor setting currents please use Separate CT up to 800 / 5A

Type: EOCR-i3MZ                                          

  • Display built-in
  • With–Over current, Undercurrent, Earth Fault, Ammeter and Communications (RS485 Mod bus)

Specification

Supply Voltage100 ~240VAC/DC
Load Current Setting Range0.5 ~80A
Delay Time(D-Time)0 ~ 200sec
Operating Time(O-Time)0.2 ~ 30sec
Inverse & Thermal1 ~ 30 classes
UndercurrentOFF, 1 ~ 10sec
Ground FaultGF delay time (EDT): 0~30s, GF O-time (ET):0.05~10s
Earth FaultSetting Range: Off,0.05~10A
Contact RatingsOverload: 1a1b, GR: 1a, (3A / 250VAC)
Phase LossOFF, 0.5 ~ 5S Adjustable
Phase Reversewithin 0.15s

For higher motor setting currents Please use separate CT up to 800 / 5A

 

Type: EOCR-i3MZ  

  • Display built-in
  • WithOvercurrent, Undercurrent, Earth Fault, Ammeter and Communications (RS485Modbus)

Specification

Supply Voltage100 ~240VAC/DC
Load Current Setting Range0.5 ~80A
Delay Time(D-Time)0 ~ 200sec
Operating Time(O-Time)0.2 ~ 30sec
Inverse & Thermal1 ~ 30classes
UndercurrentOFF, 1 ~ 10sec
Ground FaultGF delay time (EDT): 0~30s, GF O-time (ET):0.05~10s
Earth FaultSetting Range: Off,0.05~10A
Contact RatingsOverload: 1a1b, GR: 1a, (3A / 250VAC)
Phase LossOFF, 0.5 ~ 5SAdjustable
Phase Reversewithin0.15s

For higher motor setting currents Please use separate CT up to 800 / 5A

Type: EGR

PROTECTIONS

Protective ItemGround Fault Specification

FEATURES

  • MCU based compact design
  • Ground fault protection withZCT
  • Trip & Run indication
  • Manual / Electrical Reset

SPECIFICATION

Ground Fault (GF)TypeRange
Current Setting10N-M100mA – 1,000mA
Trip Time SettingO-Time0.2-2.0 sec
ResetManual / Electrical (Push Reset Button or Interrupt Supply Power)
Power Supply110/220VAC, 50/60Hz
Contact RatingModel/Rating status1-SPDT (1C), 3A/250VAC Resistive Normally De-energized
Mounting35mm DIN-Rail / Panel