Residual Current Devices
RCD employs the current balance principle which involves the supply conductors to the load (phase and neutral) wound onto a common transformer core to form the primary windings. Under healthy conditions, the current in the phase conductor is equal to the current in the neutral and the vector sum of the current is zero.
In the event of an earth fault, an amount of current will flow to earth, creating an out of balance situation in the transformer assembly. This out of balance detected by the secondary winding of the transformer will activate the trip mechanism at a pre-determined level. Single phase and neutral or three phases and neutral units (suitable for both 3 wire and 4 wire systems) are available, the latter being suitable for balanced or unbalanced 3 phase loads. The RCD tripping mechanism will operate at a residual current of between 50%-100% of its rated tripping current. (Sensitivity)
RESIDUAL TRIPPING CURRENTS
10mA —— Suitable for use in special applications where additional protection against contact is essential
30mA ——- Tripping current to provide additional protection against direct contact shock.
100mA —– Suitable for use against direct contact shock or where protection guards against fire hazards etc.
300mA —- Suitable for use in large installations where equipment protection is the main consideration and high levels of earth leakage are experienced
EPR Series
Specifications
- Rated Capacity: 25 A, 32 A, 40 A, 63 A, 80 A, 100 A
- Rigid / Flexible Conductor 35mm² / 25mm² MAXIMUM
- Calibration Temperature: 30 ̊C
- Frequency: 50/60Hz
- Electrical Endurance: 10,000
- Mechanical Endurance: 20,000
- Standards: EN 61008-1 / EN 61008-2-1 / ROHS / CE
- Poles:2P and 4P; Ue: 230 Vac (2P), 230/400 Vac (4P); 50/60 Hz
- IΔn: 30 mA, 100 mA, 300 mA, type A and AC
EPL Series
SPECIFICATIONS
- Rated Current (ln): 6, 10, 15, 16, 20, 25, 32, 40A
- Rated Voltage (Un): 230VAC
- Breaking Capacity: 6KA
- Rated Tripping Current: 30mA, 100mA, 300mA
- Characteristics: B, C CURVE
- Number of Poles: 1P+N
- Type of Terminal: LUG TYPE
- Standards: IEC61009, EN6009