Products > Energy Management > Power Factor Controllers > Nokian
Power Factor Controller

Measurement and Display
- Power Factor
- Connected Steps
- Switching Counter and duty cycles
- Current
- Voltage
- KVA
- KW
- KVAR
- Panel Temperature
- Total Voltage Harmonic Distortion
- Digital 6/12 Steps With Alarms
- With Built –in Power Analyzer
- With Continuous Digital Power Factor & Capacitor Steps Display
- With Automatic search of C/K Values
- Automatic CT Polarity adjustment and automatic Phase Rotation polarity adjustment
| Number of steps | 6 or 12 |
| Dimensions | 155 X 155 X 70 mm |
| Frequency | 50 Hz nominal (range 48…52Hz) |
| 60 Hz nominal (range 58…62 Hz) | |
| Measuring current | 0…5 A |
| Measuring and supply voltages | 110 V nominal (range 88…130 V) |
| 230 V nominal (range 185…265 V) | |
| 400 V nominal (range 320…460 V) | |
| Rated power | 13 VA |
| Relay inputs/outputs | 120Vac/5A, 250Vac/2A, |
| 110Vdc/0,3A, 60Vdc/0,6A, 24Vdc/2A | |
| Display | LCD glass with 160 symbols, backlighted |
| Protection class | IP41 front panel, IP20 rear part |
| Target cos ø-range | 0,85 ind…1,00…0,90 cap |
| Response limits, C/K | 0,01…1,99 symmetrical |
| Reconnection Delay | 10…600 s |
| Response delay | 20% of reconnection delay, min. 10 s |
| Display measurements | Cos ø, P, Q, S, THD(U), temperature |
| Installation method | Panel installation DIN-rail installation |
| Casing | Impact resistant PC/ABS, UL94V-0 |
| Operating temperature range | 0…60°C |
| Alarm log | List of 5 last alarms |
| Step counters | Yes |
| Fan control with dedicated relay | Yes |
| Accuracy (of FS) | Is: 5% |
| Iq: 5% | |
| U/I-samples: 5% | |
| Phase: 5° | |
| Distortion: ±3 dB (up to 11th ) | |
| Temperature: ±3°C | |
| CT setting range | 25/5…6000/5 |
| Power outage detection | Reaction time > 15 ms |
- IEC 61010-1
- IEC 61010-1IEC 61000-6-2
- IEC 61010-1IEC 61000-6-4
- IEC 61010-1IEC 61325
- IEC 61010-1UL 61010B-1/CSA-C22.2 NO. 1010.1